MEDIUM FILTER
MEDIUM FILTER

MEDIUM FILTER (Box type)

Product Overview 

- Various frame materials available (AL, PB, PW, SUS, G/S) depending on the installation environment.

- Used as a pre for HEPA filters in electronic components, hospitals, and food manufacturing lines.

- Compatible with both Mini Type and Separator Type designs.



  Filter Classes


Merv Rating Table(Air Filer Grade Table)

U.S. StandardsEuropean Standards
ASHRAE 52.2ASHRAE 52.1EN779
MERVRange1Range2Range3
ArrestanceDust SpotFilter Grade
0.3 to 11 to 33 to 10
13<75%>90%>90%>98%80 - 90%F7
1475 - 85%>90%>90%>99%90 - 95%F8
1585 - 95%>90%>90%>99%95%F9

  Material and use condition


ClassificationMaterial
MediaGlass Fiber / Synthetic
FrameGalvanized Steel / Aluminium  / SUS / PW / PB
TypeMini / Cell
SealantUrethane / Hot-melt
GasketNeoprene
Maximum Temperature80℃
Maximum Humidity100%